Eastron SDM630-Modbus V2

unverified library/modbus/eastron-sdm630.hal.yaml

Ideastron-sdm630
ManufacturerEastron
ModelSDM630-Modbus V2
Drivermodbus
Hazardlow
Limits unconfirmed This file has read channels only, so nothing in the file changes the device.
Read channels
ChannelTypeUnitEvery
voltage_l1 number V 2 s
voltage_l2 number V 2 s
voltage_l3 number V 2 s
current_l1 number A 2 s
current_l2 number A 2 s
current_l3 number A 2 s
power number W 2 s
power_factor number dimensionless 10 s
frequency number Hz 10 s
energy_import number kWh 60 s
energy number kWh 60 s
openhal: "0.1"
device: { name: Eastron SDM630 energy meter, model: SDM630-Modbus V2, manufacturer: Eastron }
id: eastron-sdm630
match:
  modbus_id: 2
connect:
  modbus: rtu
  port: /dev/ttyUSB0
  baud: 9600
  parity: N
  stopbits: 1
  unit: 2
  timeout: 1 s
read:
  voltage_l1: { unit: V, every: 2 s, range: [180, 260], map: { register: 0, kind: input, format: float32 } }
  voltage_l2: { unit: V, every: 2 s, range: [180, 260], map: { register: 2, kind: input, format: float32 } }
  voltage_l3: { unit: V, every: 2 s, range: [180, 260], map: { register: 4, kind: input, format: float32 } }
  current_l1: { unit: A, every: 2 s, range: [0, 100], map: { register: 6, kind: input, format: float32 } }
  current_l2: { unit: A, every: 2 s, range: [0, 100], map: { register: 8, kind: input, format: float32 } }
  current_l3: { unit: A, every: 2 s, range: [0, 100], map: { register: 10, kind: input, format: float32 } }
  power: { unit: W, every: 2 s, range: [-70000, 70000], map: { register: 52, kind: input, format: float32 } }
  power_factor: { unit: dimensionless, every: 10 s, range: [-1, 1], map: { register: 62, kind: input, format: float32 } }
  frequency: { unit: Hz, every: 10 s, range: [45, 65], map: { register: 70, kind: input, format: float32 } }
  energy_import: { unit: kWh, every: 60 s, map: { register: 72, kind: input, format: float32 } }
  energy: { unit: kWh, every: 60 s, map: { register: 342, kind: input, format: float32 } }
hazard: low
notes: >-
  Suggested limits. A person must confirm every limit before this device can be written.
  Eastron ships the meter at Modbus address 1 and 9600 baud. This file expects address 2, so it can share an
  RS-485 bus with the SDM120 file at address 1. Set the address in the meter's setup menu, or change unit
  and match.modbus_id to 1. Registers are the zero-based input register offsets from Eastron's protocol
  document, as IEEE 754 floats. This file only reads.
provenance: { source: library, by: OpenHAL starter library, at: 2026-10-25, verification: { status: unverified } }